Product Description | It is a water-based, decorative, thin-film intumescent paint that swells during fire, delaying the heating of the surface. | |||||||||||||||||||||||||
Product Number | 1102 | |||||||||||||||||||||||||
Areas of Use | It is applied as a reactive intermediate coat in passive fire protection paint systems. The product is designed for fire protection of up to 90 minutes. | |||||||||||||||||||||||||
Features / Advantages | · Provides fire resistance for up to 90 minutes.
· It is the most economical system for fire protection. · Applied as primer, intumescent coating, and topcoat. Compatible primer and topcoat must be selected. The topcoat color can be chosen from the RAL color chart.
|
|||||||||||||||||||||||||
Technical Data
|
|
|||||||||||||||||||||||||
Film Thickness and Theoretical Spreading Rate
|
Note: The above-mentioned standard thicknesses are for application purposes. To achieve the specified fire ratings, all steel sections must be coated with the correct thickness of paint. For further information and valid loading tables, please contact the C Construction Office. |
|||||||||||||||||||||||||
Preparation Instructions | The product is supplied ready for use and should be mixed thoroughly before application. | |||||||||||||||||||||||||
Surface Preparation | Metal Surface Water, salts, contaminants, oil, loose rust, and scale must be removed from the surface. The surface to be coated should be assessed in accordance with ISO 8504 and treated accordingly. Painted Surface
Other Surfaces
|
|||||||||||||||||||||||||
Application Conditions and Limitations
|
Surface moisture content: < 4% by weight. Dew point. Beware of condensation! To reduce the risk of condensation or blistering in the final surface coating, the surface and uncured substrate temperature should be at least 3°C above the dew point. | |||||||||||||||||||||||||
Uygulama Verisi
|
Note: Ensure that the hose diameter is 10 mm (8 mm if with whip end) and the hose length does not exceed 60 m. |
|||||||||||||||||||||||||
Drying Time | Drying times generally depend on air circulation, temperature, film thickness, and the number of coats applied, and may be affected accordingly. The data presented in the table below are based on the following assumptions:
|
|||||||||||||||||||||||||
Surface Temperature | 5°C | 10°C | 23°C | 40°C | ||||||||||||||||||||||
Surface Dry | 8 h | 4 h | 2 h | 1 h | ||||||||||||||||||||||
Hard Dry | 48 h | 24 h | 12 h | 8 h | ||||||||||||||||||||||
Overcoating Interval, Minimum | 16 h | 8 h | 6 h | 3 h | ||||||||||||||||||||||
Overcoating Interval, Maximum | 3 day | 2 day | 1 day | 12 h | ||||||||||||||||||||||
Safety Precautions | · The minimum overcoating interval with approved topcoats is 48 hours. Before topcoat application, it must be ensured that the required C FR 90 W paint film thickness has been achieved.”
· “Before paint application, the surface must be free from dirt and chalking.” · “For optimum intercoat adhesion, the subsequent coat should be applied before the existing paint is fully cured. If this interval is exceeded, the surface may need to be lightly roughened.” · “If the surface is exposed to high humidity and low temperature before full curing, changes in color and gloss may occur.” · “Primers and topcoats must be fully compatible with C FR 90 W to achieve the required fire performance. For information on approved primers and topcoats, please contact your local C Construction Office.” · Note: The above information provides only general application guidelines. Actual drying and curing times may vary depending on film thickness, ventilation, the existing coating system on the surface, treatments applied to the coating, and its mechanical resistance.
|
|||||||||||||||||||||||||
General Considerations | The above product information and descriptions have been prepared based on our experience and careful research, and are intended as guidance. Due to the variety of related materials, different construction and working conditions cannot be individually controlled or influenced by us. In applications beyond our control, warranty is limited solely to the quality of the product sold. No warranty is given regarding application other than product manufacturing. This technical data sheet supersedes all previous versions. The quality of the work may vary depending on your professional use of the product. In case of doubt, carry out a small test or seek technical assistance. | |||||||||||||||||||||||||
Disposal | Empty packaging may be disposed of in collection bins according to local regulations or recycling rules. Used waste material should be dried and solidified before being disposed of as construction waste. It is hazardous to destroy product residues by burning. | |||||||||||||||||||||||||
Safety Information | “Keep products out of reach of children. Keep containers tightly closed. It is recommended to use gloves and goggles during application. In case of skin contact, wash immediately with soap and water. If contact with eyes occurs, seek medical attention immediately. For further information, please refer to the Safety Data Sheet (SDS). |